| Thermal degassing |
 |
 |
RWT standard units for thermal degassing are complete performance units with optimally matched components. The units are dimensioned in such a way that an operating time of 20 to 30 minutes remains with a full feedwater reservoir without the addition of supplementary water.
Data:
| Degassing unit |
Feedwater tank |
| Type |
Diameter DE [mm] |
Output range [m3/h] |
Type |
Diameter DS [mm] |
Cylindrical length L [mm] |
Volume [m3] |
| TE1 |
300 |
2,1 |
SWB1 |
800 |
2000 |
1,1* |
| TE1 |
300 |
2,1 |
SWB2 |
1000 |
2000 |
1,8 |
| TE2 |
400 |
3,8 |
SWB3 |
1000 |
2500 |
2,2* |
| TE2 |
400 |
3,8 |
SWB4 |
1250 |
2500 |
3,5 |
| TE3 |
500 |
6 |
SWB5 |
1400 |
2500 |
4,4 |
| TE3 |
500 |
6 |
SWB6 |
1250 |
4000 |
5,3 |
| TE4 |
600 |
10 |
SWB7 |
1400 |
4000 |
6,7 |
| TE4 |
600 |
10 |
SWB8a |
1600 |
4000 |
8,8 |
| TE5 |
700 |
11 |
SWB8b |
1600 |
4000 |
8,8 |
| TE6 |
800 |
13 |
SWB8c |
1600 |
4000 |
8,8 |
| TE6 |
800 |
13 |
SWB9 |
1600 |
5000 |
10,8 |
| TE7 |
900 |
17 |
SWB10 |
1600 |
6000 |
12,8 |
| TE8 |
1000 |
20 |
SWB11 |
1900 |
5000 |
15,5 |
| TE8 |
1000 |
20 |
SWB12 |
1900 |
6000 |
18,2 |
| TE9 |
1100 |
29 |
SWB13 |
1900 |
7000 |
21,0 |
| TE10 |
1200 |
35 |
SWB14 |
2200 |
6000 |
25,0 |
| TE10 |
1200 |
35 |
SWB15 |
2500 |
6000 |
32,0 |
| TE11 |
1400 |
50 |
SWB16a |
2500 |
8000 |
42,0 |
| TE12 |
1600 |
60 |
SWB16b |
2500 |
8000 |
42,0 |
| TE13 |
1800 |
100 |
SWB17 |
2500 |
10000 |
52,0* |
| TE13 |
1800 |
100 |
SWB18 |
3000 |
8000 |
62,0* |
| TE14 |
2000 |
150 |
SWB19 |
3000 |
10000 |
75,0* |
| TE14 |
2000 |
150 |
SWB20 |
3000 |
12000 |
89,0* |
| * 20 min without the addition of any supplementary water |
Design The performance units were designed for the following conditions:
- Feedwater: approx. 105°C and 0.2 bar (g)
- Heating steam: saturated steam at 180°C and 9 bar (g)
- Desalination rate: 3%
- Exhaust vapour quantity: 0.3% of the nominal output
- Condensate quantity: 50% of the nominal output at 70°C
- Supplementary water: 15°C (43% of the mass balance)
- Max. operating overpressure: 0.5 bar (g)
- Max. operating temperature: 110°C
RWT also supplies standardized degassers up to 150 t/h, along with individual feedwater tanks, e.g. for substitution purposes. Special layouts or layouts that differ from the standard are available on request.
|
 |
| |
|
|

|
|
 |
|