Filtration
Cartridge filter

RWT manufactures cartridge filters for flow rates up to 200 m³/h. The cartridge filters are used to hold back dirt and suspended substances and as fine filters to protect sensitive units.

Design
Design cartridge filter RWT cartridge filters consist of:
  • an upper torispherical head with vessel flange, ventilation connection pieces and cover handles
  • a cylindrical section with a lower torispherical head and a vessel flange
  • flange tubes for raw water input, pure water output, flushing water output and draining
  • screwed-in filter cartridges made of Polypropylene (PP) with exchangeable filter cloth
  • three vessel support feet
Data:
Type KEF
1
KEF
2
KEF
3
KEF
4
KEF
5
KEF
6
KEF
7
KEF
8
Capacity
[m3/h]
14 20 25 35 55 90 125 200
Total height H
[mm]
1000 1000 1000 1000 1000 1000 1000 1000
Empty weight
[kg]
80 100 105 150 200 220 245 280
Vessel connection
[DN]
50 65 65 80 100 125 150 200


Design:
The cartridge filters were designed for the following conditions:
  • max. operating pressure 10 bar
  • max. operating temperature 40 °C


Filter systems for filtration, iron removal and demanganisation

RWT manufactures standardised gravel filter units (of type KIF). The units are ready-for-use. The performance data for filtration, iron removal and demanganisation specified below are based on values obtained through many years of experience and are used for orientation. Strictly, verfication of design must be carried out using current raw water values as a basis. Deacidification filters, activated carbon filters and GIH filters must always be designed to suit a particular application.

Design and Layout

Design gravel filter The filter vessels consist of:

  • upper and lower torispherical head with cylindrical shell
  • flanged-in or welded-in nozzle plate, including screwed-in filter nozzles
  • internal flushing funnel
  • all required connection nozzles for raw water input, pure water output, backwash water input and output, flushing air and venting
  • deflectors at the flushing air connection nozzles
  • vessel support feet, manholes/hand holes and name plate
Performance data:
Type   Diameter  
Ø D
[mm]

 Filtration
output
[m3/h]

  Iron removal 
output
[m3/h]
 Demanganisation
output
[m3/h]
KIF 35 356 1,5 1 0,75
KIF 45 457 2,5 1,5 1
KIF 50 508 3 2 1,5
KIF 60 600 4 2,5 2
KIF 70 700 5,5 3,5 3
KIF 80 800 7 5 4
KIF 90 900 9 6 5
KIF 100 1000 12 7 6
KIF 120 1200 17 11 9
KIF 140 1400 24 15 12
KIF 160 1600 30 20 16
KIF 180 1800 38 25 20
KIF 200 2000 45 30 25
KIF 220 2200 55 38 30
KIF 240 2400 65 45 35
KIF 260 2600 80 50 40
KIF 280 2800 90 60 45
KIF 300 3000 100 70 55
  KIF 350   3500 150 95 75


Design:
The filter vessels were designed for the following conditions:
  • Max. operating pressure: 4 bar (g) with KIF 35 and KIF 45 -
    6 bar (g) with KIF 50 and up
  • Max. operating temperature: 40 °C
A customer-specific design with deviating values for pressure and temperature is possible upon request.
 